Skip to Content

Brine cooler EA-G-380GG7-A01 C

Brine cooler EA-G-380GG7-A01 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-380GG7-A01 C

Cooling capacity i
108.53 kW
Air flow
53,785 m³/h
Fin spacing
7.0 mm
Air throw
39 m
Fans
3 × ⌀800 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Model nomenclature

How to read the code of this model.

  • B
    Number of fans: 3 — Digit 1-9.
  • C
    Fan diameter: 80 — Ø800 mm
  • E
    Coil tube rows (2nd dimensional letter): G — 8 tube rows
  • F
    Fin spacing: 7 — 7.0 mm
  • G
    Generation code: A — generation A
  • H
    Fan data (fan motor code): 01 — fan motor code; supply/poles vary with diameter

Data

Coil
Air flow 53,785 m³/h
Air throw 39 m
External surface 527.3 m²
Inner volume 163.1 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 592 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 62.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
EA-G-380GG7-A01 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
108.528 kW Sensible capacity 78.345 kW Fluid flow 34.08 m³/h Pressure drop 108.8 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
88.300 kW Sensible capacity 63.547 kW Fluid flow 27.74 m³/h Pressure drop 75.5 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated ≈ 27.67 ≈ 25.53 ≈ 25.62 ≈ 40.47
8 not rated not rated not rated not rated ≈ 69.26 ≈ 73.98 ≈ 79.27 ≈ 85.77
10 not rated not rated not rated not rated 103.62 108.53 114.64 124.10
12 not rated not rated not rated not rated not rated 140.17 148.89 160.60

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 25.22 ≈ 22.76 ≈ 22.79 ≈ 22.70
8 not rated not rated not rated not rated ≈ 40.73 ≈ 58.68 ≈ 64.23 ≈ 70.90
10 not rated not rated not rated not rated ≈ 82.50 88.30 94.28 102.48
12 not rated not rated not rated not rated not rated 114.30 122.34 132.36

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 108.528 34.08 108.8
Low speed (Y) 88.300 27.74 75.5

Dimensions

Dimension drawing of EA-G-380GG7-A01 C
Dimension drawing
Dimensions as drawn
A 4315 mm
B 1150 mm
C 1430 mm
F 1110 mm
G 1215 mm
E1 1318 mm
E2 1300 mm
E 3935 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4315 mm
Width 1150 mm
Height 1430 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.