Skip to Content

Dry cooler BC/BD-280AC5-B01 C

Dry cooler BC/BD-280AC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280AC5-B01 C

Heat rejection i
96.31 kW
Air flow
33,741 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 33,741 m³/h
External surface 278.6 m²
Inner volume 44.1 dm³
Fin materialAluminium
Net weight 367 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 52.0 dB(A)
Sound power 84.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-280AC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
96.305 kW Fluid flow 16.71 m³/h Pressure drop 28.4 kPa
Heat rejection · Low speed (Y)
76.979 kW Fluid flow 13.36 m³/h Pressure drop 19.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 54.46 not rated not rated not rated not rated not rated
40 96.31 54.91 not rated not rated not rated not rated
45 137.17 96.55 55.31 not rated not rated not rated
50 177.72 137.23 96.77 55.68 not rated not rated
55 218.12 177.62 137.31 97.01 56.04 not rated
60 258.44 217.87 177.57 137.46 97.31 56.42

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 43.91 not rated not rated not rated not rated not rated
40 76.98 44.25 not rated not rated not rated not rated
45 109.13 77.11 44.56 not rated not rated not rated
50 140.99 109.09 77.24 44.84 not rated not rated
55 172.71 140.79 109.09 77.40 45.12 not rated
60 204.35 172.37 140.68 109.16 77.62 45.43

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 96.305 16.71 28.4
Low speed (Y) 76.979 13.36 19.1

Dimensions

Dimension drawing of BC/BD-280AC5-B01 C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 2500 mm
H 1200 mm
I 1190 mm
K 3050 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2750 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.