BC/BD-363CB1-B19 C
96.25 kW
Defrost: None
Product code: BC/BD-280AC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 33,741 m³/h |
|---|---|
| External surface | 278.6 m² |
| Inner volume | 44.1 dm³ |
| Fin material | Aluminium |
| Net weight | 367 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 84.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-280AC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 54.46 | not rated | not rated | not rated | not rated | not rated |
| 40 | 96.31 | 54.91 | not rated | not rated | not rated | not rated |
| 45 | 137.17 | 96.55 | 55.31 | not rated | not rated | not rated |
| 50 | 177.72 | 137.23 | 96.77 | 55.68 | not rated | not rated |
| 55 | 218.12 | 177.62 | 137.31 | 97.01 | 56.04 | not rated |
| 60 | 258.44 | 217.87 | 177.57 | 137.46 | 97.31 | 56.42 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.91 | not rated | not rated | not rated | not rated | not rated |
| 40 | 76.98 | 44.25 | not rated | not rated | not rated | not rated |
| 45 | 109.13 | 77.11 | 44.56 | not rated | not rated | not rated |
| 50 | 140.99 | 109.09 | 77.24 | 44.84 | not rated | not rated |
| 55 | 172.71 | 140.79 | 109.09 | 77.40 | 45.12 | not rated |
| 60 | 204.35 | 172.37 | 140.68 | 109.16 | 77.62 | 45.43 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 96.305 | 16.71 | 28.4 |
| Low speed (Y) | 76.979 | 13.36 | 19.1 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 3050 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 2750 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.