BC/BD-t-191RC5-B04 C
96.13 kW
Defrost: None
Product code: BC/BD-380AD5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 23,608 m³/h |
|---|---|
| External surface | 522.0 m² |
| Inner volume | 68.7 dm³ |
| Fin material | Aluminium |
| Net weight | 544 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | C |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-380AD5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 58.51 | not rated | not rated | not rated | not rated | not rated |
| 40 | 96.14 | 58.54 | not rated | not rated | not rated | not rated |
| 45 | 132.75 | 95.95 | 58.59 | not rated | not rated | not rated |
| 50 | 169.02 | 132.36 | 95.82 | 58.68 | not rated | not rated |
| 55 | 205.14 | 168.44 | 132.08 | 95.79 | 58.82 | not rated |
| 60 | 241.17 | 204.38 | 168.03 | 131.96 | 95.89 | 59.05 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 44.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 72.29 | 44.55 | not rated | not rated | not rated | not rated |
| 45 | 99.28 | 72.21 | 44.63 | not rated | not rated | not rated |
| 50 | 126.02 | 99.09 | 72.20 | 44.75 | not rated | not rated |
| 55 | 152.63 | 125.72 | 99.00 | 72.26 | 44.92 | not rated |
| 60 | 179.18 | 152.23 | 125.55 | 99.03 | 72.44 | 45.16 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 96.138 | 16.67 | 88.0 |
| Low speed (Y) | 72.286 | 12.53 | 53.0 |
| A | 3950 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3700 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 4250 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4250 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.