Skip to Content

Dry cooler BC/BD-380AD5-B03 C

Dry cooler BC/BD-380AD5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-380AD5-B03 C

Heat rejection i
96.14 kW
Air flow
23,608 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 23,608 m³/h
External surface 522.0 m²
Inner volume 68.7 dm³
Fin materialAluminium
Net weight 544 kg
Fans
Quantity 3
Diameter 800 mm
Speed 435 rpm
Power 1,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 37.0 dB(A)
Sound power 69.0 dB(A)
Energy class C
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-380AD5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
96.138 kW Fluid flow 16.67 m³/h Pressure drop 88.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
72.286 kW Fluid flow 12.53 m³/h Pressure drop 53.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 58.51 not rated not rated not rated not rated not rated
40 96.14 58.54 not rated not rated not rated not rated
45 132.75 95.95 58.59 not rated not rated not rated
50 169.02 132.36 95.82 58.68 not rated not rated
55 205.14 168.44 132.08 95.79 58.82 not rated
60 241.17 204.38 168.03 131.96 95.89 59.05

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 44.48 not rated not rated not rated not rated not rated
40 72.29 44.55 not rated not rated not rated not rated
45 99.28 72.21 44.63 not rated not rated not rated
50 126.02 99.09 72.20 44.75 not rated not rated
55 152.63 125.72 99.00 72.26 44.92 not rated
60 179.18 152.23 125.55 99.03 72.44 45.16

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 96.138 16.67 88.0
Low speed (Y) 72.286 12.53 53.0

Dimensions

Dimension drawing of BC/BD-380AD5-B03 C
Dimension drawing
Dimensions as drawn
A 3950 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 3700 mm
H 1200 mm
I 1190 mm
K 4250 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4250 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.