BC/BD-t-2x180LC1-B03 C
96.24 kW
Defrost: None
Product code: BC/BD-363CB1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 34,894 m³/h |
|---|---|
| External surface | 278.0 m² |
| Inner volume | 34.5 dm³ |
| Fin material | Aluminium |
| Net weight | 330 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-363CB1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 54.69 | not rated | not rated | not rated | not rated | not rated |
| 40 | 96.25 | 55.00 | not rated | not rated | not rated | not rated |
| 45 | 136.92 | 96.31 | 55.27 | not rated | not rated | not rated |
| 50 | 177.31 | 136.76 | 96.36 | 55.51 | not rated | not rated |
| 55 | 217.57 | 176.93 | 136.62 | 96.43 | 55.75 | not rated |
| 60 | 257.75 | 216.99 | 176.61 | 136.54 | 96.55 | 56.00 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 47.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 82.35 | 47.34 | not rated | not rated | not rated | not rated |
| 45 | 116.79 | 82.37 | 47.56 | not rated | not rated | not rated |
| 50 | 150.95 | 116.61 | 82.40 | 47.77 | not rated | not rated |
| 55 | 184.99 | 150.58 | 116.47 | 82.46 | 47.98 | not rated |
| 60 | 218.97 | 184.44 | 150.28 | 116.39 | 82.56 | 48.20 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 96.247 | 16.70 | 56.1 |
| Low speed (Y) | 82.351 | 14.29 | 42.5 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 3300 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3300 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.