BC/BD-380AD5-B03 C
96.14 kW
Defrost: None
Product code: BC/BD-t-191RC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 26,464 m³/h |
|---|---|
| External surface | 210.2 m² |
| Inner volume | 29.3 dm³ |
| Fin material | Aluminium |
| Net weight | 273 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.3 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-191RC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 56.58 | not rated | not rated | not rated | not rated | not rated |
| 40 | 96.13 | 56.71 | not rated | not rated | not rated | not rated |
| 45 | 134.58 | 95.94 | 56.81 | not rated | not rated | not rated |
| 50 | 172.68 | 134.09 | 95.75 | 56.91 | not rated | not rated |
| 55 | 210.60 | 171.92 | 133.69 | 95.65 | 57.05 | not rated |
| 60 | 248.43 | 209.58 | 171.28 | 133.39 | 95.62 | 57.23 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 44.59 | not rated | not rated | not rated | not rated | not rated |
| 40 | 74.95 | 44.68 | not rated | not rated | not rated | not rated |
| 45 | 104.39 | 74.78 | 44.76 | not rated | not rated | not rated |
| 50 | 133.51 | 103.99 | 74.64 | 44.84 | not rated | not rated |
| 55 | 162.49 | 132.90 | 103.67 | 74.56 | 44.94 | not rated |
| 60 | 191.38 | 161.67 | 132.40 | 103.44 | 74.56 | 45.10 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 96.134 | 16.68 | 68.0 |
| Low speed (Y) | 74.953 | 13.00 | 43.6 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.