BC/BD-780AC1-B01 C
356.93 kW
Defrost: None
Product code: BC/BD-t-2X750AD5-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 86,928 m³/h |
|---|---|
| External surface | 878.5 m² |
| Inner volume | 146.4 dm³ |
| Fin material | Aluminium |
| Net weight | 867 kg |
| Quantity | 14 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 9,900 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-t-2X750AD5-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 214.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 356.63 | 215.14 | not rated | not rated | not rated | not rated |
| 45 | 494.04 | 355.78 | 215.40 | not rated | not rated | not rated |
| 50 | 629.99 | 492.23 | 355.14 | 215.76 | not rated | not rated |
| 55 | 765.27 | 627.28 | 490.82 | 354.85 | 216.31 | not rated |
| 60 | 900.18 | 761.69 | 625.15 | 489.96 | 355.00 | 217.11 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 356.634 | 61.85 | 70.6 |
| A | 6050 mm |
|---|---|
| B | 1220 mm |
| C | 1710 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 5700 mm |
| H | 800 mm |
| I | 1660 mm |
| K | 6400 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 6050 mm |
|---|---|
| Width | 1800 mm |
| Height | 1220 mm |