BE-180CC5-B01 C
92.20 kW
Defrost: None
Product code: BE-180DD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 21,829 m³/h |
|---|---|
| External surface | 528.6 m² |
| Inner volume | 60.0 dm³ |
| Fin material | Aluminium |
| Net weight | 434 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-180DD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 56.34 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.15 | 56.16 | not rated | not rated | not rated | not rated |
| 45 | 126.90 | 91.58 | 56.00 | not rated | not rated | not rated |
| 50 | 161.31 | 125.98 | 91.08 | 55.87 | not rated | not rated |
| 55 | 195.56 | 160.05 | 125.18 | 90.67 | 55.78 | not rated |
| 60 | 229.72 | 193.97 | 158.95 | 124.51 | 90.37 | 55.78 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.47 | not rated | not rated | not rated | not rated | not rated |
| 40 | 70.48 | 43.32 | not rated | not rated | not rated | not rated |
| 45 | 96.63 | 70.00 | 43.17 | not rated | not rated | not rated |
| 50 | 122.52 | 95.88 | 69.59 | 43.04 | not rated | not rated |
| 55 | 148.28 | 121.50 | 95.23 | 69.22 | 42.97 | not rated |
| 60 | 173.98 | 147.01 | 120.62 | 94.65 | 68.97 | 42.96 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 92.152 | 15.98 | 61.1 |
| Low speed (Y) | 70.475 | 12.22 | 38.0 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2260 mm |
| F | 1050 mm |
| G | 2860 mm |
| E1 | 1830 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.