Skip to Content

Dry cooler BE-2x280AB1-B01C C

Dry cooler BE-2x280AB1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x280AB1-B01C C

Heat rejection i
255.69 kW
Air flow
82,939 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 82,939 m³/h
External surface 864.2 m²
Inner volume 123.5 dm³
Fin materialAluminium
Net weight 1,214 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x280AB1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
255.686 kW Fluid flow 44.37 m³/h Pressure drop 89.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
204.049 kW Fluid flow 35.42 m³/h Pressure drop 59.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 148.75 not rated not rated not rated not rated not rated
40 255.69 149.12 not rated not rated not rated not rated
45 360.26 255.36 149.42 not rated not rated not rated
50 464.05 359.28 255.07 149.71 not rated not rated
55 567.48 462.45 358.45 254.89 150.05 not rated
60 670.71 565.29 461.11 357.84 254.89 150.49

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 119.76 not rated not rated not rated not rated not rated
40 204.05 120.01 not rated not rated not rated not rated
45 286.24 203.69 120.22 not rated not rated not rated
50 367.77 285.36 203.40 120.45 not rated not rated
55 448.94 366.34 284.62 203.24 120.73 not rated
60 529.95 447.03 365.17 284.07 203.23 121.08

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 255.686 44.37 89.1
Low speed (Y) 204.049 35.42 59.8

Dimensions

Dimension drawing of BE-2x280AB1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 2850 mm
F 2230 mm
G 3450 mm
E1 1250 mm
H 3100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3450 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.