Skip to Content

Dry cooler BE-380AD1-B01 C

Dry cooler BE-380AD1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-380AD1-B01 C

Heat rejection i
255.49 kW
Air flow
61,800 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 61,800 m³/h
External surface 1,412.0 m²
Inner volume 171.5 dm³
Fin materialAluminium
Net weight 1,012 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 85.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-380AD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
255.485 kW Fluid flow 44.31 m³/h Pressure drop 37.7 kPa
Heat rejection · Low speed (Y)
194.783 kW Fluid flow 33.78 m³/h Pressure drop 23.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 153.89 not rated not rated not rated not rated not rated
40 255.49 153.80 not rated not rated not rated not rated
45 353.85 254.35 153.72 not rated not rated not rated
50 451.13 351.79 253.38 153.70 not rated not rated
55 547.91 448.21 350.03 252.63 153.78 not rated
60 644.42 544.14 445.69 348.64 252.18 154.04

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 118.67 not rated not rated not rated not rated not rated
40 194.78 118.57 not rated not rated not rated not rated
45 268.27 193.84 118.47 not rated not rated not rated
50 340.90 266.62 193.05 118.44 not rated not rated
55 413.12 338.58 265.22 192.45 118.50 not rated
60 485.13 410.16 336.62 264.14 192.11 118.72

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 255.485 44.31 37.7
Low speed (Y) 194.783 33.78 23.2

Dimensions

Dimension drawing of BE-380AD1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 4060 mm
F 1050 mm
G 4660 mm
E1 1230 mm
E2 1200 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4660 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.