BE-180DD1-B01 C
92.15 kW
Defrost: None
Product code: BE-t-180HB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 22,141 m³/h |
|---|---|
| External surface | 317.3 m² |
| Inner volume | 39.9 dm³ |
| Fin material | Aluminium |
| Net weight | 374 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-t-180HB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 55.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 91.24 | 54.91 | not rated | not rated | not rated | not rated |
| 45 | 126.34 | 90.74 | 54.82 | not rated | not rated | not rated |
| 50 | 161.06 | 125.47 | 90.29 | 54.75 | not rated | not rated |
| 55 | 195.61 | 159.85 | 124.71 | 89.93 | 54.72 | not rated |
| 60 | 230.05 | 194.05 | 158.78 | 124.08 | 89.67 | 54.75 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 42.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 70.48 | 42.82 | not rated | not rated | not rated | not rated |
| 45 | 97.10 | 70.05 | 42.73 | not rated | not rated | not rated |
| 50 | 123.42 | 96.37 | 69.66 | 42.65 | not rated | not rated |
| 55 | 149.59 | 122.41 | 95.73 | 69.34 | 42.61 | not rated |
| 60 | 175.68 | 148.31 | 121.52 | 95.20 | 69.11 | 42.63 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 91.240 | 15.82 | 54.2 |
| Low speed (Y) | 70.482 | 12.23 | 34.2 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2260 mm |
| F | 1050 mm |
| G | 2860 mm |
| E1 | 1830 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.