SP.-EA-DA-x-145AE7-B23 C
5.21 kW
Defrost: None
Product code: EA-DA-x-235BE7-B21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,080 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 25.3 m² |
| Inner volume | 9.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 75 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø15,9 |
| EA-DA-x-235BE7-B21 C | None |
|---|---|
| EA-DA-x-235BE7-B21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | 2.24 | 2.48 | 2.70 | 2.86 | 2.97 | 3.01 | 3.10 | 3.32 | 3.62 | 3.56 | 3.53 | 3.50 | 3.45 |
| 5 | not rated | not rated | 2.98 | 3.29 | 3.48 | 3.65 | 3.77 | 3.91 | 4.18 | 4.58 | 4.52 | 4.49 | 4.44 | 4.35 |
| 6 | not rated | not rated | 3.05 | ≈ 3.74 | 4.06 | 4.31 | 4.49 | 4.66 | 5.00 | 5.48 | 5.42 | 5.39 | 5.33 | 5.21 |
| 7 | 1.18 | ≈ 1.16 | ≈ 2.40 | ≈ 4.19 | 4.60 | 4.93 | 5.17 | 5.40 | 5.79 | 6.37 | 6.32 | 6.28 | 6.21 | 6.06 |
| 8 | 1.32 | 1.30 | ≈ 1.30 | ≈ 4.60 | 5.10 | 5.51 | 5.83 | 6.12 | 6.57 | 7.24 | 7.21 | 7.17 | 7.09 | 6.93 |
| 9 | 1.45 | 1.43 | ≈ 1.43 | ≈ 3.61 | ≈ 5.55 | 6.06 | 6.45 | 6.81 | 7.32 | 8.09 | 8.08 | 8.05 | 7.97 | 7.79 |
| 10 | 1.57 | 1.55 | 1.56 | not rated | 5.97 | 6.56 | 7.04 | 7.47 | 8.05 | 8.91 | 8.94 | 8.91 | 8.84 | 8.66 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.941 |
| SC2 | 0 | 8 | 6.115 |
| SC3 | -18 | 7 | 4.364 |
| SC4 | -25 | 6 | 3.049 |
| SC5 | -34 | 6 | — |
| A | 1457 mm |
|---|---|
| B | 730 mm |
| C | 530 mm |
| F | 560 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø15,9 |
| Length | 1457 mm |
|---|---|
| Width | 730 mm |
| Height | 530 mm |