EA-530AC10-C05 C
8.08 kW
Defrost: None
Product code: EA-145AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,978 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 26.6 m² |
| Inner volume | 5.8 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø22 |
| EA-145AC4-C01 C | None |
|---|---|
| EA-145AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.19 | 3.29 | 3.36 | 3.42 | 3.44 | 3.42 | 3.39 | 3.44 | 3.66 | 3.95 | 3.84 | 3.79 | 3.73 | 3.64 |
| 5 | 4.00 | 4.21 | 4.39 | 4.54 | 4.63 | 4.67 | 4.65 | 4.69 | 4.98 | 5.39 | 5.24 | 5.18 | 5.11 | 5.00 |
| 6 | 4.66 | 4.97 | 5.20 | 5.44 | 5.59 | 5.69 | 5.72 | 5.83 | 6.20 | 6.73 | 6.59 | 6.53 | 6.44 | 6.31 |
| 7 | 5.25 | 5.62 | 6.00 | 6.33 | 6.56 | 6.71 | 6.78 | 6.90 | 7.35 | 7.99 | 7.81 | 7.74 | 7.63 | 7.45 |
| 8 | ≈ 5.64 | 6.26 | 6.75 | 7.19 | 7.51 | 7.73 | 7.85 | 7.99 | 8.51 | 9.26 | 9.06 | 8.97 | 8.84 | 8.62 |
| 9 | ≈ 6.20 | 6.85 | 7.46 | 8.02 | 8.44 | 8.73 | 8.90 | 9.09 | 9.68 | 10.54 | 10.32 | 10.23 | 10.07 | 9.81 |
| 10 | ≈ 4.91 | ≈ 7.38 | 8.12 | 8.79 | 9.32 | 9.70 | 9.94 | 10.18 | 10.85 | 11.82 | 11.60 | 11.49 | 11.33 | 11.02 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.602 |
| SC2 | 0 | 8 | 7.994 |
| SC3 | -18 | 7 | 6.434 |
| SC4 | -25 | 6 | 5.201 |
| SC5 | -34 | 6 | 4.728 |
| A | 1067 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E | 735 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø22 |
| Length | 1067 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.