EA-240AC6-C01 C
9.25 kW
Defrost: Electric
Product code: EA-235AG7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,910 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 38.2 m² |
| Inner volume | 12.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 68 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-235AG7-C01 C | None |
|---|---|
| EA-235AG7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.01 | 4.01 | 4.02 | 4.04 | 4.03 | 3.99 | 3.92 | 4.02 | 4.28 | 4.63 | 4.52 | 4.48 | 4.44 | 4.37 |
| 5 | 5.07 | 5.14 | 5.21 | 5.27 | 5.28 | 5.24 | 5.17 | 5.25 | 5.57 | 6.02 | 5.83 | 5.76 | 5.67 | 5.53 |
| 6 | 6.09 | 6.25 | 6.40 | 6.52 | 6.57 | 6.55 | 6.48 | 6.54 | 6.93 | 7.49 | 7.22 | 7.11 | 6.96 | 6.72 |
| 7 | 7.10 | 7.35 | 7.59 | 7.78 | 7.87 | 7.89 | 7.82 | 7.88 | 8.34 | 9.00 | 8.68 | 8.54 | 8.34 | 8.01 |
| 8 | 7.99 | 8.36 | 8.70 | 9.00 | 9.18 | 9.23 | 9.18 | 9.24 | 9.78 | 10.56 | 10.19 | 10.02 | 9.78 | 9.36 |
| 9 | 8.78 | 9.27 | 9.71 | 10.10 | 10.34 | 10.43 | 10.45 | 10.56 | 11.19 | 12.11 | 11.70 | 11.52 | 11.23 | 10.73 |
| 10 | 9.51 | 10.13 | 10.69 | 11.13 | 11.44 | 11.62 | 11.67 | 11.81 | 12.51 | 13.53 | 13.14 | 12.95 | 12.66 | 12.13 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.141 |
| SC2 | 0 | 8 | 9.243 |
| SC3 | -18 | 7 | 7.835 |
| SC4 | -25 | 6 | 6.397 |
| SC5 | -34 | 6 | 6.135 |
| A | 1357 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.