EA-350AG10-C09 C
34.56 kW
Defrost: Electric
Product code: EA-263EG4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,587 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 267.0 m² |
| Inner volume | 53.0 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 253 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.9 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-263EG4-C01 C | None |
|---|---|
| EA-263EG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.61 | 15.67 | 15.77 | 15.90 | 15.92 | 15.86 | 15.72 | 16.05 | 17.09 | 18.55 | 18.14 | 18.01 | 17.83 | 17.57 |
| 5 | 19.55 | 19.81 | 20.09 | 20.34 | 20.40 | 20.34 | 20.15 | 20.42 | 21.68 | 23.49 | 22.84 | 22.60 | 22.26 | 21.73 |
| 6 | 23.25 | 23.84 | 24.38 | 24.84 | 25.04 | 25.02 | 24.81 | 25.01 | 26.50 | 28.66 | 27.76 | 27.41 | 26.89 | 26.03 |
| 7 | 26.73 | 27.72 | 28.47 | 29.21 | 29.60 | 29.70 | 29.52 | 29.72 | 31.46 | 34.02 | 32.90 | 32.42 | 31.72 | 30.55 |
| 8 | 29.95 | 31.19 | 32.44 | 33.54 | 34.21 | 34.43 | 34.33 | 34.55 | 36.57 | 39.51 | 38.21 | 37.63 | 36.75 | 35.28 |
| 9 | 32.64 | 34.44 | 36.09 | 37.51 | 38.42 | 38.87 | 38.96 | 39.31 | 41.66 | 45.07 | 43.61 | 42.93 | 41.89 | 40.14 |
| 10 | 35.22 | 37.51 | 39.59 | 41.38 | 42.55 | 43.20 | 43.40 | 43.81 | 46.42 | 50.20 | 48.74 | 48.05 | 46.98 | 45.08 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 48.744 |
| SC2 | 0 | 8 | 34.551 |
| SC3 | -18 | 7 | 29.404 |
| SC4 | -25 | 6 | 24.376 |
| SC5 | -34 | 6 | 23.409 |
| A | 2015 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2015 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.