EA-430AE10-C01 C
9.21 kW
Defrost: Electric
Product code: EA-430AC4-C05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,361 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 44.4 m² |
| Inner volume | 9.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 50 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-430AC4-C05 C | None |
|---|---|
| EA-430AC4-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.82 | 3.93 | 4.02 | 4.10 | 4.14 | 4.13 | 4.10 | 4.20 | 4.47 | 4.85 | 4.74 | 4.71 | 4.66 | 4.59 |
| 5 | 4.77 | 4.99 | 5.17 | 5.33 | 5.41 | 5.43 | 5.40 | 5.50 | 5.84 | 6.34 | 6.16 | 6.09 | 6.00 | 5.86 |
| 6 | 5.60 | 5.92 | 6.21 | 6.46 | 6.62 | 6.68 | 6.71 | 6.83 | 7.26 | 7.88 | 7.65 | 7.56 | 7.43 | 7.21 |
| 7 | 6.32 | 6.76 | 7.11 | 7.45 | 7.69 | 7.83 | 7.89 | 8.02 | 8.52 | 9.27 | 9.04 | 8.94 | 8.79 | 8.54 |
| 8 | 6.97 | 7.48 | 8.00 | 8.45 | 8.77 | 8.97 | 9.07 | 9.22 | 9.80 | 10.65 | 10.40 | 10.28 | 10.10 | 9.79 |
| 9 | ≈ 7.40 | 8.19 | 8.84 | 9.41 | 9.82 | 10.09 | 10.24 | 10.43 | 11.09 | 12.04 | 11.77 | 11.64 | 11.43 | 11.06 |
| 10 | ≈ 8.03 | 8.85 | 9.63 | 10.32 | 10.84 | 11.20 | 11.40 | 11.63 | 12.37 | 13.45 | 13.16 | 13.01 | 12.77 | 12.35 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.157 |
| SC2 | 0 | 8 | 9.223 |
| SC3 | -18 | 7 | 7.560 |
| SC4 | -25 | 6 | 6.207 |
| SC5 | -34 | 6 | 5.678 |
| A | 2107 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 437.5 mm |
| E | 1785 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.