EA-530AC10-C05 C
8.08 kW
Defrost: None
Product code: EA-430AC7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,741 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 27.8 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-430AC7-C05 C | None |
|---|---|
| EA-430AC7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.41 | 3.37 | 3.36 | 3.36 | 3.34 | 3.30 | 3.26 | 3.31 | 3.51 | 3.80 | 3.71 | 3.68 | 3.62 | 3.55 |
| 5 | 4.39 | 4.40 | 4.43 | 4.46 | 4.46 | 4.42 | 4.37 | 4.41 | 4.68 | 5.06 | 4.91 | 4.86 | 4.79 | 4.69 |
| 6 | 5.37 | 5.45 | 5.52 | 5.60 | 5.63 | 5.61 | 5.56 | 5.60 | 5.93 | 6.41 | 6.20 | 6.13 | 6.02 | 5.85 |
| 7 | 6.28 | 6.45 | 6.61 | 6.76 | 6.83 | 6.84 | 6.80 | 6.84 | 7.24 | 7.83 | 7.58 | 7.48 | 7.34 | 7.11 |
| 8 | 7.11 | 7.36 | 7.61 | 7.84 | 7.98 | 8.06 | 8.07 | 8.11 | 8.59 | 9.29 | 9.01 | 8.90 | 8.72 | 8.43 |
| 9 | 7.85 | 8.21 | 8.54 | 8.81 | 9.00 | 9.12 | 9.18 | 9.28 | 9.85 | 10.68 | 10.43 | 10.31 | 10.14 | 9.80 |
| 10 | 8.54 | 9.01 | 9.40 | 9.77 | 10.04 | 10.20 | 10.28 | 10.41 | 11.05 | 11.99 | 11.71 | 11.58 | 11.39 | 11.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.709 |
| SC2 | 0 | 8 | 8.105 |
| SC3 | -18 | 7 | 6.794 |
| SC4 | -25 | 6 | 5.518 |
| SC5 | -34 | 6 | 5.392 |
| A | 2107 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 437.5 mm |
| E | 1785 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.