ED-DP-145AC7-B24 C
5.81 kW
Defrost: None
Product code: ED-DP-235AC7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,362 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 22.9 m² |
| Inner volume | 8.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 82 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 945 rpm |
| Power | 130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 63.0 dB(A) |
| Energy class | A |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-235AC7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.48 | 2.45 | 2.44 | 2.44 | 2.43 | 2.41 | 2.38 | 2.41 | 2.56 | 2.77 | 2.71 | 2.69 | 2.66 | 2.60 |
| 5 | 3.19 | 3.19 | 3.21 | 3.23 | 3.22 | 3.20 | 3.17 | 3.20 | 3.39 | 3.67 | 3.56 | 3.53 | 3.48 | 3.41 |
| 6 | 3.88 | 3.93 | 3.99 | 4.04 | 4.06 | 4.05 | 4.02 | 4.04 | 4.28 | 4.63 | 4.49 | 4.43 | 4.36 | 4.24 |
| 7 | 4.57 | 4.68 | 4.78 | 4.86 | 4.91 | 4.92 | 4.90 | 4.93 | 5.22 | 5.64 | 5.47 | 5.40 | 5.30 | 5.14 |
| 8 | 5.20 | 5.38 | 5.55 | 5.69 | 5.78 | 5.82 | 5.80 | 5.84 | 6.18 | 6.69 | 6.49 | 6.41 | 6.29 | 6.09 |
| 9 | 5.77 | 6.01 | 6.24 | 6.45 | 6.58 | 6.66 | 6.69 | 6.76 | 7.16 | 7.74 | 7.53 | 7.44 | 7.31 | 7.08 |
| 10 | 6.29 | 6.60 | 6.90 | 7.13 | 7.32 | 7.43 | 7.49 | 7.58 | 8.05 | 8.73 | 8.54 | 8.45 | 8.32 | 8.08 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.536 |
| SC2 | 0 | 8 | 5.837 |
| SC3 | -18 | 7 | 4.889 |
| SC4 | -25 | 6 | 3.988 |
| SC5 | -34 | 6 | 3.898 |
| A | 1548 mm |
|---|---|
| B | 900 mm |
| C | 325 mm |
| F | 940 mm |
| G | 410 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1548 mm |
|---|---|
| Width | 900 mm |
| Height | 410 mm |
Our engineers answer with a selection for your conditions.