ED-DP-435AE4-B22 C
16.36 kW
Defrost: None
Product code: ED-DP-440AC7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,994 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 60.6 m² |
| Inner volume | 19.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 162 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.3 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-DP-440AC7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.94 | 6.87 | 6.84 | 6.83 | 6.78 | 6.71 | 6.62 | 6.69 | 7.09 | 7.66 | 7.46 | 7.39 | 7.28 | 7.12 |
| 5 | 8.96 | 8.99 | 9.05 | 9.11 | 9.09 | 9.03 | 8.93 | 8.98 | 9.51 | 10.27 | 9.96 | 9.85 | 9.71 | 9.49 |
| 6 | 10.97 | 11.14 | 11.29 | 11.45 | 11.52 | 11.49 | 11.41 | 11.45 | 12.12 | 13.09 | 12.68 | 12.53 | 12.31 | 11.96 |
| 7 | 12.84 | 13.20 | 13.54 | 13.84 | 14.00 | 14.03 | 13.98 | 14.04 | 14.87 | 16.07 | 15.58 | 15.39 | 15.09 | 14.61 |
| 8 | 14.50 | 15.04 | 15.55 | 16.02 | 16.33 | 16.51 | 16.56 | 16.68 | 17.67 | 19.12 | 18.57 | 18.34 | 17.98 | 17.40 |
| 9 | 16.02 | 16.76 | 17.45 | 18.01 | 18.42 | 18.69 | 18.83 | 19.03 | 20.21 | 21.93 | 21.43 | 21.20 | 20.85 | 20.26 |
| 10 | 17.43 | 18.40 | 19.20 | 19.98 | 20.54 | 20.91 | 21.11 | 21.37 | 22.69 | 24.63 | 24.08 | 23.82 | 23.43 | 22.76 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.080 |
| SC2 | 0 | 8 | 16.681 |
| SC3 | -18 | 7 | 13.920 |
| SC4 | -25 | 6 | 11.286 |
| SC5 | -34 | 6 | 11.023 |
| A | 2748 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 570 mm |
| E1 | 2435 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2748 mm |
|---|---|
| Width | 1050 mm |
| Height | 570 mm |
Our engineers answer with a selection for your conditions.