ED-DR-463BA4-A29 C
38.74 kW
Defrost: None
Product code: ED-DR-363AA5-A29 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 53,834 m³/h |
|---|---|
| Air throw | 30 m |
| External surface | 194.5 m² |
| Inner volume | 43.3 dm³ |
| Fin spacing | 5.0 mm |
| Fin material | Aluminium |
| Net weight | 336 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 5,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 97.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| ED-DR-363AA5-A29 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | ≈ 16.86 | ≈ 17.08 | ≈ 17.27 | ≈ 17.30 | ≈ 17.23 | ≈ 17.14 | ≈ 17.08 | ≈ 18.06 | ≈ 19.48 | ≈ 18.95 | ≈ 18.76 | ≈ 18.47 | ≈ 18.05 |
| 5 | ≈ 20.88 | ≈ 21.51 | ≈ 22.14 | ≈ 22.67 | ≈ 22.95 | ≈ 23.04 | ≈ 23.02 | ≈ 22.99 | ≈ 24.34 | ≈ 26.28 | ≈ 25.56 | ≈ 25.29 | ≈ 24.90 | ≈ 24.30 |
| 6 | ≈ 24.48 | ≈ 25.68 | 26.76 | ≈ 27.72 | ≈ 28.37 | ≈ 28.79 | ≈ 29.06 | ≈ 29.29 | ≈ 31.10 | ≈ 33.66 | ≈ 32.81 | ≈ 32.48 | ≈ 31.99 | ≈ 31.22 |
| 7 | ≈ 27.68 | ≈ 29.40 | ≈ 30.96 | ≈ 32.32 | ≈ 33.28 | ≈ 33.93 | ≈ 34.36 | ≈ 34.69 | ≈ 36.86 | ≈ 40.03 | ≈ 39.29 | ≈ 38.98 | ≈ 38.53 | ≈ 37.79 |
| 8 | ≈ 30.60 | ≈ 32.88 | ≈ 34.97 | ≈ 36.80 | ≈ 38.13 | ≈ 39.06 | ≈ 39.69 | 40.16 | ≈ 42.70 | ≈ 46.43 | ≈ 45.61 | ≈ 45.27 | ≈ 44.76 | ≈ 43.91 |
| 9 | ≈ 33.23 | ≈ 36.11 | ≈ 38.77 | ≈ 41.13 | ≈ 42.88 | ≈ 44.14 | ≈ 45.01 | ≈ 45.66 | ≈ 48.59 | ≈ 52.89 | ≈ 52.03 | ≈ 51.66 | ≈ 51.10 | ≈ 50.15 |
| 10 | ≈ 35.58 | ≈ 39.08 | ≈ 42.35 | ≈ 45.28 | ≈ 47.51 | ≈ 49.14 | ≈ 50.31 | ≈ 51.16 | ≈ 54.50 | ≈ 59.39 | 58.51 | ≈ 58.13 | ≈ 57.53 | ≈ 56.49 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | ≈ 17.04 | ≈ 17.27 | ≈ 17.46 | ≈ 17.50 | ≈ 17.43 | ≈ 17.34 | ≈ 17.28 | ≈ 18.27 | ≈ 19.70 | ≈ 19.17 | ≈ 18.96 | ≈ 18.68 | ≈ 18.24 |
| 5 | ≈ 21.07 | ≈ 21.73 | ≈ 22.39 | ≈ 22.94 | ≈ 23.23 | ≈ 23.33 | ≈ 23.31 | ≈ 23.29 | ≈ 24.64 | ≈ 26.61 | ≈ 25.88 | ≈ 25.60 | ≈ 25.21 | ≈ 24.59 |
| 6 | ≈ 24.67 | ≈ 25.90 | 27.01 | ≈ 28.00 | ≈ 28.66 | ≈ 29.10 | ≈ 29.38 | ≈ 29.61 | ≈ 31.44 | ≈ 34.11 | ≈ 33.26 | ≈ 32.92 | ≈ 32.42 | ≈ 31.64 |
| 7 | ≈ 27.88 | ≈ 29.65 | ≈ 31.24 | ≈ 32.64 | ≈ 33.63 | ≈ 34.29 | ≈ 34.73 | ≈ 35.07 | ≈ 37.27 | ≈ 40.48 | ≈ 39.73 | ≈ 39.42 | ≈ 38.96 | ≈ 38.21 |
| 8 | ≈ 30.80 | ≈ 33.15 | ≈ 35.28 | ≈ 37.16 | ≈ 38.52 | ≈ 39.48 | ≈ 40.12 | 40.60 | ≈ 43.18 | ≈ 46.95 | ≈ 46.13 | ≈ 45.79 | ≈ 45.27 | ≈ 44.41 |
| 9 | ≈ 33.44 | ≈ 36.39 | ≈ 39.10 | ≈ 41.52 | ≈ 43.32 | ≈ 44.61 | ≈ 45.51 | ≈ 46.17 | ≈ 49.14 | ≈ 53.49 | ≈ 52.63 | ≈ 52.26 | ≈ 51.69 | ≈ 50.73 |
| 10 | ≈ 35.79 | ≈ 39.36 | ≈ 42.71 | ≈ 45.70 | ≈ 47.99 | ≈ 49.66 | ≈ 50.86 | ≈ 51.74 | ≈ 55.11 | ≈ 60.06 | 59.19 | ≈ 58.80 | ≈ 58.20 | ≈ 57.15 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 58.509 | 59.186 |
| SC2 | 0 | 8 | 40.155 | 40.604 |
| SC3 | -18 | 7 | 32.746 | 33.077 |
| SC4 | -25 | 6 | 26.760 | 27.013 |
| SC5 | -34 | 6 | 24.767 | 24.962 |
| A | 3728 mm |
|---|---|
| B | 1730 mm |
| C | 788 mm |
| F | 1530 mm |
| G | 805 mm |
| E1 | 1138 mm |
| E2 | 1120 mm |
| E | 3395 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 3728 mm |
|---|---|
| Width | 1730 mm |
| Height | 805 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.