ED-630AC4-C21 C
17.08 kW
Defrost: Electric
Product code: ED-150AG4-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 6,142 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 91.1 m² |
| Inner volume | 19.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 103 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 680 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 78.7 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-150AG4-C21 C | None |
|---|---|
| ED-150AG4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.78 | 6.80 | 6.85 | 6.92 | 6.94 | 6.93 | 6.88 | 7.05 | 7.51 | 8.16 | 8.01 | 7.96 | 7.89 | 7.81 |
| 5 | 8.68 | 8.80 | 8.94 | 9.08 | 9.13 | 9.12 | 9.06 | 9.20 | 9.77 | 10.60 | 10.32 | 10.22 | 10.09 | 9.88 |
| 6 | 10.56 | 10.78 | 11.04 | 11.28 | 11.40 | 11.42 | 11.36 | 11.47 | 12.16 | 13.17 | 12.78 | 12.63 | 12.40 | 12.04 |
| 7 | 12.29 | 12.74 | 13.15 | 13.51 | 13.71 | 13.76 | 13.72 | 13.82 | 14.64 | 15.84 | 15.36 | 15.16 | 14.85 | 14.35 |
| 8 | 13.88 | 14.50 | 15.09 | 15.60 | 15.93 | 16.11 | 16.11 | 16.19 | 17.15 | 18.55 | 17.99 | 17.75 | 17.37 | 16.74 |
| 9 | 15.29 | 16.13 | 16.89 | 17.48 | 17.94 | 18.18 | 18.27 | 18.46 | 19.57 | 21.19 | 20.63 | 20.38 | 19.95 | 19.19 |
| 10 | 16.59 | 17.66 | 18.53 | 19.38 | 19.96 | 20.30 | 20.44 | 20.65 | 21.90 | 23.71 | 23.10 | 22.81 | 22.35 | 21.56 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 23.099 |
| SC2 | 0 | 8 | 16.188 |
| SC3 | -18 | 7 | 13.603 |
| SC4 | -25 | 6 | 11.041 |
| SC5 | -34 | 6 | 10.631 |
| A | 1368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 1035 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1368 mm |
|---|---|
| Width | 1350 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.