ED-435AE4-C21 C
22.11 kW
Defrost: None
Product code: ED-340AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 8,870 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 109.6 m² |
| Inner volume | 23.8 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 136 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| ED-340AE4-C21 C | None |
|---|---|
| ED-340AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.83 | 8.87 | 8.95 | 9.03 | 9.06 | 9.03 | 8.96 | 9.22 | 9.83 | 10.68 | 10.49 | 10.42 | 10.34 | 10.22 |
| 5 | 11.35 | 11.55 | 11.75 | 11.94 | 12.01 | 11.99 | 11.90 | 12.12 | 12.88 | 13.98 | 13.61 | 13.48 | 13.31 | 13.06 |
| 6 | 13.85 | 14.25 | 14.62 | 14.91 | 15.08 | 15.11 | 15.01 | 15.19 | 16.11 | 17.46 | 16.92 | 16.72 | 16.41 | 15.93 |
| 7 | 16.14 | 16.77 | 17.36 | 17.89 | 18.21 | 18.31 | 18.22 | 18.39 | 19.49 | 21.11 | 20.43 | 20.15 | 19.74 | 19.07 |
| 8 | 18.12 | 19.01 | 19.83 | 20.55 | 20.93 | 21.17 | 21.22 | 21.48 | 22.79 | 24.71 | 24.02 | 23.69 | 23.18 | 22.32 |
| 9 | 19.96 | 21.14 | 22.10 | 23.04 | 23.66 | 24.00 | 24.11 | 24.40 | 25.88 | 28.04 | 27.29 | 26.95 | 26.42 | 25.50 |
| 10 | 21.65 | 23.01 | 24.36 | 25.54 | 26.33 | 26.81 | 27.00 | 27.34 | 28.99 | 31.40 | 30.58 | 30.19 | 29.58 | 28.52 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 30.583 |
| SC2 | 0 | 8 | 21.480 |
| SC3 | -18 | 7 | 18.045 |
| SC4 | -25 | 6 | 14.620 |
| SC5 | -34 | 6 | 13.956 |
| A | 2148 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 467 mm |
| E1 | 1835 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2148 mm |
|---|---|
| Width | 1210 mm |
| Height | 467 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.