ED-340AE4-C21 C
22.29 kW
Defrost: None
Product code: ED-435AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 8,758 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 109.6 m² |
| Inner volume | 23.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 140 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| ED-435AE4-C21 C | None |
|---|---|
| ED-435AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.79 | 8.82 | 8.88 | 8.96 | 8.98 | 8.96 | 8.89 | 9.14 | 9.74 | 10.59 | 10.40 | 10.35 | 10.27 | 10.18 |
| 5 | 11.31 | 11.48 | 11.67 | 11.84 | 11.91 | 11.89 | 11.80 | 12.01 | 12.76 | 13.85 | 13.48 | 13.36 | 13.19 | 12.94 |
| 6 | 13.81 | 14.17 | 14.52 | 14.79 | 14.95 | 14.97 | 14.88 | 15.05 | 15.97 | 17.30 | 16.77 | 16.57 | 16.27 | 15.80 |
| 7 | 16.10 | 16.69 | 17.26 | 17.76 | 18.05 | 18.14 | 18.06 | 18.22 | 19.31 | 20.91 | 20.25 | 19.99 | 19.59 | 18.92 |
| 8 | 18.10 | 18.94 | 19.72 | 20.41 | 20.78 | 21.01 | 21.06 | 21.31 | 22.60 | 24.51 | 23.81 | 23.48 | 22.99 | 22.16 |
| 9 | 19.95 | 21.08 | 21.99 | 22.89 | 23.49 | 23.82 | 23.93 | 24.20 | 25.67 | 27.81 | 27.08 | 26.75 | 26.23 | 25.34 |
| 10 | 21.66 | 22.97 | 24.26 | 25.39 | 26.15 | 26.61 | 26.80 | 27.12 | 28.76 | 31.15 | 30.35 | 29.97 | 29.37 | 28.34 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 30.350 |
| SC2 | 0 | 8 | 21.307 |
| SC3 | -18 | 7 | 17.910 |
| SC4 | -25 | 6 | 14.517 |
| SC5 | -34 | 6 | 13.903 |
| A | 2748 mm |
|---|---|
| B | 1030 mm |
| C | 285 mm |
| F | 985 mm |
| G | 367 mm |
| E1 | 2435 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2748 mm |
|---|---|
| Width | 1030 mm |
| Height | 367 mm |