ED-340AE7-C21 C
19.16 kW
Defrost: Electric
Product code: ED-435AE7-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 9,522 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 68.7 m² |
| Inner volume | 23.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 134 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| ED-435AE7-C21 C | None |
|---|---|
| ED-435AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.29 | 7.22 | 7.20 | 7.20 | 7.17 | 7.11 | 7.04 | 7.19 | 7.65 | 8.28 | 8.10 | 8.03 | 7.93 | 7.79 |
| 5 | 9.62 | 9.64 | 9.69 | 9.75 | 9.74 | 9.68 | 9.57 | 9.71 | 10.31 | 11.16 | 10.86 | 10.76 | 10.63 | 10.43 |
| 6 | 11.90 | 12.06 | 12.24 | 12.40 | 12.46 | 12.42 | 12.31 | 12.42 | 13.17 | 14.24 | 13.80 | 13.64 | 13.41 | 13.06 |
| 7 | 14.15 | 14.49 | 14.82 | 15.12 | 15.24 | 15.26 | 15.17 | 15.28 | 16.18 | 17.50 | 16.94 | 16.72 | 16.39 | 15.87 |
| 8 | 16.22 | 16.76 | 17.29 | 17.78 | 18.06 | 18.16 | 18.09 | 18.22 | 19.30 | 20.87 | 20.23 | 19.96 | 19.56 | 18.89 |
| 9 | 18.02 | 18.79 | 19.50 | 20.16 | 20.57 | 20.76 | 20.85 | 21.09 | 22.37 | 24.26 | 23.57 | 23.25 | 22.78 | 21.98 |
| 10 | 19.70 | 20.72 | 21.55 | 22.40 | 22.95 | 23.29 | 23.44 | 23.72 | 25.17 | 27.29 | 26.63 | 26.33 | 25.86 | 25.05 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 26.630 |
| SC2 | 0 | 8 | 18.220 |
| SC3 | -18 | 7 | 15.168 |
| SC4 | -25 | 6 | 12.238 |
| SC5 | -34 | 6 | 11.947 |
| A | 2748 mm |
|---|---|
| B | 1030 mm |
| C | 285 mm |
| F | 985 mm |
| G | 367 mm |
| E1 | 2435 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2748 mm |
|---|---|
| Width | 1030 mm |
| Height | 367 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.