- Catalogue
- Dry coolers
- BE (Dry)
BE (Dry)
- Refrigerants
- ETHYLENE GLYCOL 30%, PROPYLENE GLYCOL 30%, WATER
- Capacity
- 69.30–1727.54 kW
- Fans
- ⌀800, ⌀910 mm
- Max. working pressure
- 10 bar
Model nomenclature
How to read the model codes of this series, with an example.
-
A
Series BE = BE = V-type dry cooler.
-
B
Fin type (optional "t") — = absent: standard corrugated finst = t: louvered fins (high-efficiency fin surface)
-
C
Fan rows (optional "Nx") — Catalogue: "Fan Row no." (number before x/X). — = absent: 1 fan row2x = 2 fan rows
-
D
Number of fans per row — Digit 1-9; total fans = fan rows x this digit.
-
E
Fan diameter — Two digits = diameter / 10 (91 = Ø910). 80 = Ø800 mm91 = Ø910 mm
-
G
Coil tube rows (2nd dimensional letter) B = 3 tube rowsC = 4 tube rowsD = 5 tube rows
-
H
Fin spacing — Catalogue fin-spacing code. 1 = 2.1 mm5 = 2.5 mm
-
I
Generation code — Catalogue: "Generation Code". B = generation BC = generation C
-
J
Fan data (fan motor code) — Catalogue: "Fan Data". Two digits select the fan motor (supply, poles); the meaning is series-specific. 01 = three-phase 400 V 50 Hz, 6-pole AC fan (in this series)04 = three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
-
K
Delivery version (optional) — = absent: standardC = C: container delivery versionT = T: truck delivery version
| Model | Heat rejection [kW] i Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 % | Fans | Air flow [m³/h] | Variants |
|---|---|---|---|---|
| BE-480AC5-B01 C | 303.65 kW | 4 × ⌀800 | 85,123 |
Variants (1)
|
| BE-2x291DB5-C04C C | 303.87 kW | 4 × ⌀910 | 115,681 |
Variants (1) |
| BE-t-380HC1-B01 C | 305.33 kW | 3 × ⌀800 | 65,514 |
Variants (1)
|
| BE-2x291BB1-B04T C | 305.64 kW | 4 × ⌀910 | 111,514 |
Variants (1) |
| BE-2X280AC1-B01T C | 306.50 kW | 4 × ⌀800 | 82,651 |
Variants (1) |
| BE-t-391GC5-B04 C | 306.73 kW | 3 × ⌀910 | 81,597 |
Variants (1)
|
| BE-t-2x280GC1-B01C C | 306.76 kW | 4 × ⌀800 | 76,136 |
Variants (1) |
| BE-2x280CB5-B01C C | 307.02 kW | 4 × ⌀800 | 89,592 |
Variants (1) |
| BE-380CD1-B01 C | 307.33 kW | 3 × ⌀800 | 66,818 |
Variants (1)
|
| BE-t-480GB1-B01 C | 307.42 kW | 4 × ⌀800 | 84,025 |
Variants (1)
|
| BE-2x280BD1-B01T C | 307.92 kW | 4 × ⌀800 | 79,754 |
Variants (1) |
| BE-t-2x291GB5-C04C C | 309.97 kW | 4 × ⌀910 | 106,089 |
Variants (1) |
| BE-380FD1-B01 C | 310.14 kW | 3 × ⌀800 | 66,211 |
Variants (1)
|
| BE-2x280AD1-B01C C | 310.98 kW | 4 × ⌀800 | 77,302 |
Variants (1) |
| BE-t-2x280GC5-B01T C | 311.07 kW | 4 × ⌀800 | 81,050 |
Variants (1) |
| BE-2x380BB5-B01C C | 311.79 kW | 6 × ⌀800 | 124,631 |
Variants (1) |
| BE-t-391HB5-B04 C | 312.42 kW | 3 × ⌀910 | 88,173 |
Variants (1)
|
| BE-t-2x280HB5-B01C C | 312.69 kW | 4 × ⌀800 | 87,169 |
Variants (1) |
| BE-491AB5-B04 C | 312.83 kW | 4 × ⌀910 | 113,664 |
Variants (1)
|
| BE-2x291AC5-C04C C | 313.87 kW | 4 × ⌀910 | 103,828 |
Variants (1) |
| BE-2x280DC5-B01T C | 314.06 kW | 4 × ⌀800 | 88,127 |
Variants (1) |
| BE-391AD1-B04 C | 314.38 kW | 3 × ⌀910 | 80,056 |
Variants (1)
|
| BE-2x280AD5-B01T C | 314.72 kW | 4 × ⌀800 | 81,569 |
Variants (1) |
| BE-491BB1-B04 C | 317.07 kW | 4 × ⌀910 | 112,995 |
Variants (1)
|
| BE-391DC1-B04 C | 317.42 kW | 3 × ⌀910 | 87,271 |
Variants (1)
|
| BE-480BD1-B01 C | 318.35 kW | 4 × ⌀800 | 81,363 |
Variants (1)
|
| BE-2x280DC1-B01C C | 320.45 kW | 4 × ⌀800 | 86,221 |
Variants (1) |
| BE-580BB1-B01 C | 320.62 kW | 5 × ⌀800 | 106,959 |
Variants (1)
|
| BE-2x280CB5-B01T C | 320.79 kW | 4 × ⌀800 | 90,224 |
Variants (1) |
| BE-391FB5-B04 C | 321.95 kW | 3 × ⌀910 | 89,859 |
Variants (1)
|
| BE-2x291BC1-C04C C | 322.04 kW | 4 × ⌀910 | 103,269 |
Variants (1) |
| BE-391DD5-B04 C | 323.41 kW | 3 × ⌀910 | 86,616 |
Variants (1)
|
| BE-480AC1-B01 C | 323.95 kW | 4 × ⌀800 | 84,314 |
Variants (1)
|
| BE-2x291BC5-B04T C | 324.92 kW | 4 × ⌀910 | 109,588 |
Variants (1) |
| BE-2x291AB1-B04T C | 325.96 kW | 4 × ⌀910 | 110,614 |
Variants (1) |
| BE-2x280DD5-B01C C | 326.14 kW | 4 × ⌀800 | 85,540 |
Variants (1) |
| BE-391CB1-B04 C | 327.72 kW | 3 × ⌀910 | 90,214 |
Variants (1)
|
| BE-t-391GC1-B04 C | 327.89 kW | 3 × ⌀910 | 80,549 |
Variants (1)
|
| BE-480AD5-B01 C | 328.29 kW | 4 × ⌀800 | 83,365 |
Variants (1)
|
| BE-2x291DB5-B04T C | 328.34 kW | 4 × ⌀910 | 117,973 |
Variants (1) |
| BE-t-480GC5-B01 C | 328.68 kW | 4 × ⌀800 | 82,463 |
Variants (1)
|
| BE-t-2x280HB5-B01T C | 330.46 kW | 4 × ⌀800 | 88,415 |
Variants (1) |
| BE-580AB5-B01 C | 330.77 kW | 5 × ⌀800 | 108,492 |
Variants (1)
|
| BE-2x280AD1-B01T C | 330.87 kW | 4 × ⌀800 | 80,458 |
Variants (1) |
| BE-t-2x280GC1-B01T C | 330.89 kW | 4 × ⌀800 | 79,850 |
Variants (1) |
| BE-2x280CB1-B01C C | 330.91 kW | 4 × ⌀800 | 89,278 |
Variants (1) |
| BE-480CB5-B01 C | 330.92 kW | 4 × ⌀800 | 90,616 |
Variants (1)
|
| BE-2x291DB1-C04C C | 334.70 kW | 4 × ⌀910 | 114,811 |
Variants (1) |
| BE-2x380BB5-B01T C | 335.94 kW | 6 × ⌀800 | 127,983 |
Variants (1) |
| BE-2x280DC1-B01T C | 336.32 kW | 4 × ⌀800 | 87,667 |
Variants (1) |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
Downloads
- BE-480AC5-B01 C — product datasheet (PDF)
- BE-2x291DB5-C04C C — product datasheet (PDF)
- BE-t-380HC1-B01 C — product datasheet (PDF)
- BE-2x291BB1-B04T C — product datasheet (PDF)
- BE-2X280AC1-B01T C — product datasheet (PDF)
- BE-t-391GC5-B04 C — product datasheet (PDF)
- BE-t-2x280GC1-B01C C — product datasheet (PDF)
- BE-2x280CB5-B01C C — product datasheet (PDF)
- BE-380CD1-B01 C — product datasheet (PDF)
- BE-t-480GB1-B01 C — product datasheet (PDF)
- BE-2x280BD1-B01T C — product datasheet (PDF)
- BE-t-2x291GB5-C04C C — product datasheet (PDF)
- BE-380FD1-B01 C — product datasheet (PDF)
- BE-2x280AD1-B01C C — product datasheet (PDF)
- BE-t-2x280GC5-B01T C — product datasheet (PDF)
- BE-2x380BB5-B01C C — product datasheet (PDF)
- BE-t-391HB5-B04 C — product datasheet (PDF)
- BE-t-2x280HB5-B01C C — product datasheet (PDF)
- BE-491AB5-B04 C — product datasheet (PDF)
- BE-2x291AC5-C04C C — product datasheet (PDF)
- BE-2x280DC5-B01T C — product datasheet (PDF)
- BE-391AD1-B04 C — product datasheet (PDF)
- BE-2x280AD5-B01T C — product datasheet (PDF)
- BE-491BB1-B04 C — product datasheet (PDF)
- BE-391DC1-B04 C — product datasheet (PDF)
- BE-480BD1-B01 C — product datasheet (PDF)
- BE-2x280DC1-B01C C — product datasheet (PDF)
- BE-580BB1-B01 C — product datasheet (PDF)
- BE-2x280CB5-B01T C — product datasheet (PDF)
- BE-391FB5-B04 C — product datasheet (PDF)
- BE-2x291BC1-C04C C — product datasheet (PDF)
- BE-391DD5-B04 C — product datasheet (PDF)
- BE-480AC1-B01 C — product datasheet (PDF)
- BE-2x291BC5-B04T C — product datasheet (PDF)
- BE-2x291AB1-B04T C — product datasheet (PDF)
- BE-2x280DD5-B01C C — product datasheet (PDF)
- BE-391CB1-B04 C — product datasheet (PDF)
- BE-t-391GC1-B04 C — product datasheet (PDF)
- BE-480AD5-B01 C — product datasheet (PDF)
- BE-2x291DB5-B04T C — product datasheet (PDF)
- BE-t-480GC5-B01 C — product datasheet (PDF)
- BE-t-2x280HB5-B01T C — product datasheet (PDF)
- BE-580AB5-B01 C — product datasheet (PDF)
- BE-2x280AD1-B01T C — product datasheet (PDF)
- BE-t-2x280GC1-B01T C — product datasheet (PDF)
- BE-2x280CB1-B01C C — product datasheet (PDF)
- BE-480CB5-B01 C — product datasheet (PDF)
- BE-2x291DB1-C04C C — product datasheet (PDF)
- BE-2x380BB5-B01T C — product datasheet (PDF)
- BE-2x280DC1-B01T C — product datasheet (PDF)
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.