EA-340AG6-C01 C
18.66 kW
Defrost: Electric
Product code: EA-540AC10-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,777 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 44.6 m² |
| Inner volume | 19.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 124 kg |
| Quantity | 5 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-540AC10-C01 C | None |
|---|---|
| EA-540AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.50 | 7.54 | 7.57 | 7.59 | 7.54 | 7.45 | 7.33 | 7.37 | 7.78 | 8.36 | 8.07 | 7.96 | 7.81 | 7.57 |
| 5 | 9.70 | 9.91 | 10.07 | 10.23 | 10.29 | 10.26 | 10.17 | 10.22 | 10.82 | 11.67 | 11.29 | 11.16 | 10.97 | 10.69 |
| 6 | 11.70 | 12.15 | 12.57 | 12.92 | 13.12 | 13.19 | 13.15 | 13.25 | 14.04 | 15.17 | 14.72 | 14.55 | 14.30 | 13.88 |
| 7 | 13.42 | 14.07 | 14.68 | 15.23 | 15.54 | 15.78 | 15.92 | 16.13 | 17.15 | 18.63 | 18.24 | 18.08 | 17.80 | 17.32 |
| 8 | 14.97 | 15.88 | 16.61 | 17.35 | 17.89 | 18.25 | 18.47 | 18.74 | 19.92 | 21.67 | 21.24 | 21.06 | 20.79 | 20.33 |
| 9 | 16.40 | 17.46 | 18.53 | 19.49 | 20.20 | 20.69 | 21.01 | 21.35 | 22.72 | 24.73 | 24.28 | 24.08 | 23.77 | 23.25 |
| 10 | 17.60 | 19.02 | 20.35 | 21.56 | 22.46 | 23.11 | 23.55 | 23.97 | 25.52 | 27.80 | 27.33 | 27.12 | 26.78 | 26.19 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 27.334 |
| SC2 | 0 | 8 | 18.735 |
| SC3 | -18 | 7 | 15.329 |
| SC4 | -25 | 6 | 12.565 |
| SC5 | -34 | 6 | 11.810 |
| A | 3117 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2785 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 3117 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.