ED-163AE4-C27 C
17.69 kW
Defrost: None
Product code: ED-245AC4-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 9,339 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 64.9 m² |
| Inner volume | 14.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 111 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 700 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| ED-245AC4-C23 C | None |
|---|---|
| ED-245AC4-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.60 | 6.62 | 6.65 | 6.70 | 6.70 | 6.67 | 6.63 | 6.72 | 7.14 | 7.73 | 7.55 | 7.49 | 7.40 | 7.27 |
| 5 | 8.69 | 8.85 | 8.97 | 9.10 | 9.16 | 9.15 | 9.09 | 9.17 | 9.73 | 10.53 | 10.27 | 10.18 | 10.05 | 9.86 |
| 6 | 10.65 | 11.01 | 11.34 | 11.62 | 11.77 | 11.82 | 11.77 | 11.86 | 12.58 | 13.61 | 13.23 | 13.10 | 12.88 | 12.57 |
| 7 | 12.30 | 12.84 | 13.34 | 13.72 | 14.02 | 14.21 | 14.30 | 14.47 | 15.37 | 16.70 | 16.33 | 16.19 | 15.97 | 15.55 |
| 8 | 13.83 | 14.50 | 15.19 | 15.80 | 16.23 | 16.50 | 16.64 | 16.85 | 17.90 | 19.45 | 19.03 | 18.86 | 18.60 | 18.18 |
| 9 | 15.09 | 16.13 | 17.04 | 17.84 | 18.41 | 18.78 | 19.00 | 19.25 | 20.46 | 22.23 | 21.77 | 21.57 | 21.27 | 20.76 |
| 10 | 16.42 | 17.66 | 18.80 | 19.82 | 20.55 | 21.06 | 21.36 | 21.68 | 23.04 | 25.05 | 24.55 | 24.32 | 23.98 | 23.39 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.550 |
| SC2 | 0 | 8 | 16.845 |
| SC3 | -18 | 7 | 13.855 |
| SC4 | -25 | 6 | 11.335 |
| SC5 | -34 | 6 | 10.745 |
| A | 1948 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 441 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 1948 mm |
|---|---|
| Width | 1210 mm |
| Height | 441 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.