ED-440AC4-C21 C
25.68 kW
Defrost: Electric
Product code: ED-440AE7-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 12,803 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 91.6 m² |
| Inner volume | 32.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 166 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | B |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-440AE7-C21 C | None |
|---|---|
| ED-440AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.75 | 9.65 | 9.61 | 9.62 | 9.58 | 9.51 | 9.43 | 9.58 | 10.18 | 11.03 | 10.78 | 10.68 | 10.55 | 10.36 |
| 5 | 12.86 | 12.88 | 12.94 | 13.03 | 13.03 | 12.96 | 12.84 | 12.96 | 13.75 | 14.88 | 14.48 | 14.35 | 14.16 | 13.89 |
| 6 | 15.90 | 16.12 | 16.35 | 16.58 | 16.66 | 16.64 | 16.52 | 16.63 | 17.62 | 19.05 | 18.48 | 18.27 | 17.98 | 17.52 |
| 7 | 18.92 | 19.37 | 19.80 | 20.21 | 20.39 | 20.44 | 20.36 | 20.48 | 21.69 | 23.46 | 22.74 | 22.47 | 22.06 | 21.38 |
| 8 | 21.67 | 22.39 | 23.10 | 23.76 | 24.16 | 24.32 | 24.28 | 24.44 | 25.89 | 28.02 | 27.21 | 26.87 | 26.35 | 25.45 |
| 9 | 24.08 | 25.09 | 26.05 | 26.93 | 27.50 | 27.79 | 27.97 | 28.27 | 30.01 | 32.56 | 31.73 | 31.33 | 30.71 | 29.63 |
| 10 | 26.33 | 27.67 | 28.79 | 29.92 | 30.68 | 31.18 | 31.44 | 31.81 | 33.77 | 36.64 | 35.83 | 35.43 | 34.81 | 33.72 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 35.827 |
| SC2 | 0 | 8 | 24.437 |
| SC3 | -18 | 7 | 20.275 |
| SC4 | -25 | 6 | 16.353 |
| SC5 | -34 | 6 | 15.971 |
| A | 2748 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 467 mm |
| E1 | 2435 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2748 mm |
|---|---|
| Width | 1210 mm |
| Height | 467 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.